S-2.3, r. 2 - Regulation respecting standards, specifications and quality criteria applicable to 9-1-1 emergency centres and to certain secondary emergency call centres

Full text
5. A 9-1-1 emergency centre must
(1)  be situated in a building that, at the time of its installation, complies with the standards applicable to post-disaster buildings, according to the definition made applicable by Chapter I of the Construction Code (chapter B-1.1, r. 2);
(2)  ensure that the building in which it is situated complies with those standards if it undergoes major alterations;
(3)  be situated in a building equipped with a fire alarm and detection system, a heat detector, a smoke detector and a carbon monoxide detector and fire extinguishing equipment; and
(4)  have a control device for the heating, ventilation and air conditioning systems that allows to shut the air intake.
O.C. 1042-2010, s. 5.